The FD30 controller operates Across-The-Line where full voltage is applied to the motor for starting by the use of a single motor contactor. Starting inrush current is approximately 600% of rated full load amperes. The FD30 can be programmed for either fully automatic or semiautomatic operation.

Specification

Product Type

Electric Fire Pump Controller

Starting Method

Across-the-Line (Full Voltage)

Display

7-inch Color Touchscreen

Controller Type

Fire Pump Controller with Integrated ATS

Starting Voltage

100% Line Voltage

Starting Current

Approximately 600% FLA

Starting Torque

100%

Power Supply

200–600 VAC 3Ø / 240 VAC 1Ø

Customer Inputs

10 Programmable Inputs

Output Relays

4 Standard DPDT Relays

Optional Boards

Relay Board, Modbus, Alarm Board, 4-20mA Board

USB Port

Yes

Pressure Settings

Fully Programmable

Timers

Minimum Run, Sequential Start, Weekly Test, etc.

History & Diagnostics

Available through Touchscreen

Standard Enclosure

UL Type 2

Optional Enclosure

Type 3, 3R, 4, 4X, 12

Standards

UL218, UL1008, FM, CSA, NFPA 20, CE