Firetrol combined automatic and manual MarkIII+ based diesel engine fire pump controllers are intended for starting and monitoring fire pump diesel engines. They are suitable for use with both mechanical and electronic type engines. The controller is available for 12 or 24 volt negative ground systems, using lead acid or Nickel-Cadmium batteries. The controller monitors, displays and records fire pump system information.

Specification

Controller Type

Diesel Engine Fire Pump Controller

Engine Voltage

12V or 24V

Operation

Manual & Automatic

Operating Temperature

4°C to 40°C

Standards

NFPA 20

Certifications

UL218, CSA C22.2 No.14, FM Approved, City of New York Approved

Enclosure

NEMA Type 2 (IEC IP22), Drip-proof

Operator Interface

7" LCD Color Touchscreen HMI

Battery Monitoring

Dual Battery Voltage & Charging Status

Pressure Sensor

Solid-State Pressure Transducer

Pressure Range

0–500 psi (Calibrated 0–300 psi)

Pressure Units

PSI, kPa, Bar, Feet of Head, Meters of Water

Event Logging

Lifetime Pressure & Event Recording

USB Port

USB Flash Drive Export

Communication

Modbus TCP/IP

Remote Signals

Manual Remote Start, Auto Start, Deluge Valve Start

Audible Alarm

Included

Manufacturer

Firetrol