Firetrol FTA1300 Wye-Delta, Open Transition Starting Fire Pump Controllers are used with delta-wound squirrel cage motors. FTA1300 controllers are of the open circuit transition type in which the motor circuit is opened during the transition from start to run. The controller monitors, displays and records fire pump system information.Actuating the controller by the pressure switch, START push-button or deluge valve contact closes the start contactor connecting the mo-tor to the line in the wye connection. The motor will draw approximately 33% of its normal inrush current and develop approximately 33% of its normal starting torque. After a time delay, the motor is automatically reconnected in delta, applying full voltage to the motor windings. These controllers are recommended especially for use with generator sets

Specification

Controller Type

Electric Fire Pump Controller

Starting Method

Wye-Delta Open Transition Starting

Starting Current

Approximately 33% Normal Inrush Current

Starting Torque

Approximately 33% Normal Starting Torque

Motor Connection

Starts in Wye, Automatically Transfers to Delta

Recommended For

Generator Set Applications

Operation

Manual & Automatic

Operating Temperature

4°C to 40°C

Standards

NFPA 20, NFPA 70

Certifications

UL218, cUL, CE, FM Approved

Enclosure

NEMA Type 2 (IEC IP22)

Operator Interface

7" Color Touchscreen HMI

Pressure Sensor

Solid-State Pressure Transducer

Pressure Range

0–500 psi (Calibrated 0–300 psi)

Communication

Modbus TCP/IP

USB Port

Available

Event Logging

Pressure & Event History

Manufacturer

Firetrol